ON LINE UPS 1KVA 1PH:1PH 36V MAX+
- Weight8.1kg
- Output VoltageSame as Input
- Dimensions (L*W*H)14.5x39.7x22
SALIENT FEATURES:
- High Frequency and Double Conversion Online Technology.
- High End IGBT Based.
- High End Micro Controller Based.
- Wide Input Voltage Range
- Advanced PFC Technology
Microtek High Frequency Online UPS provides Uninterrupted Pure Power for Critical Applications such as Computer Network, Servers, Cyber Cafes, ATM Machine, Labs etc. MAX+ Online UPS Series system, commonly called the Double conversion system, begins by converting AC power to a stable DC, and then converts back to AC, in order to maintain a significant load, with a stable sinusoidal output, from the input line via AC. / DC converter, or from batteries if power fails.
Rated Capacity: 1 KVA / 900 Watts
Phase: Single Phase In, Single Phase Out
- Emergency Power Supply: - Whenever there is a power outage or shutdown, the UPS stands as a reliable and reliable power source. You can continue your work by using UPS or Batteries in the uncertain state of remote power disconnection.
- Protects the Voltage Sensitive Device from Bad Electricity: - You can detect power fluctuations in variable power leading to damage to the gadgets. The uninterruptible power supply provides stable output by controlling power fluctuations.
- Provides Surgical Protection: - In the event of a power outage, UPS detects improper power supply and stops direct power supply. Then it gives us stable energy from its stock. It prevents the cause of damage to the devices due to power supply interruptions.
- Battery Life Save: - You can continue working in operating mode even when the power is off as it keeps charging every time you connect the UPS to the battery.
Microtek High Frequency Online UPS provides Uninterrupted Pure Power for Critical Applications such as Computer Network, Servers, Cyber Cafes, ATM Machine, Labs etc. MAX+ Online UPS Series system, commonly called the Double conversion system, begins by converting AC power to a stable DC, and then converts back to AC, in order to maintain a significant load, with a stable sinusoidal output, from the input line via AC. / DC converter, or from batteries if power fails.
Rated Capacity: 1 KVA / 900 Watts
Phase: Single Phase In, Single Phase Out
- Emergency Power Supply: - Whenever there is a power outage or shutdown, the UPS stands as a reliable and reliable power source. You can continue your work by using UPS or Batteries in the uncertain state of remote power disconnection.
- Protects the Voltage Sensitive Device from Bad Electricity: - You can detect power fluctuations in variable power leading to damage to the gadgets. The uninterruptible power supply provides stable output by controlling power fluctuations.
- Provides Surgical Protection: - In the event of a power outage, UPS detects improper power supply and stops direct power supply. Then it gives us stable energy from its stock. It prevents the cause of damage to the devices due to power supply interruptions.
- Battery Life Save: - You can continue working in operating mode even when the power is off as it keeps charging every time you connect the UPS to the battery.
- High Frequency and Double Conversion Online Technology.
- High End IGBT Based.
- High End Micro Controller Based.
- Wide Input Voltage Range
- Advanced PFC Technology
- Advanced Battery Management
- Automatic Battery Charging in UPS Off Mode
- Short Circuit and Overload Protection
- Smart RS232 Communication with monitoring software
- SNMP Card Slot (Optional)
- Over Temperature Protection.
- EMI / RFI Noise Filter
- LCD/LED Display simultaneously
- Specially designed to suit Indian Power and Environment Conditions
- Generator Compatible (Supplying Sinewave Voltage)
- Isolation Transformer (Optional)
- Different Output Voltage settings.
- Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
- Static Bypass Enable or Disable.
- Outlets Programmable and Non Programmable.
- Protection from DC Fan failure.
- In-built Over Voltage Cut-Off Device.
INPUT | |
MODEL | NM36MX1KK11 |
RATED CAPACITY | 1 KVA / 900 Watts |
INPUT VOLTAGE RANGE (Load <50%) | 118 ~ 295 V (± 5 V) |
INPUT VOLTAGE RANGE (Load >50%) | 160 ~ 295 V (± 5 V) |
FREQUENCY | 40 ~ 70 Hz |
PHASE | Single Phase with Ground |
POWER FACTOR | ≥0.99 @ full load |
OUTPUT | |
OUTPUT VOLATGE RANGE | 208 / 220 / 230 / 240 V AC |
FREQUENCY RANGE (Synchronized Range) FREQUENCY RANGE (Battery Mode) |
47 ~ 53 Hz or 57 ~ 63 Hz 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
THD (Linear Load) | ≤2% |
THD (Non Linear Load) | ≤4% |
OVERLOAD | >110%, 30s turn to Bypass Mode >150% instant turn to Bypass |
CREST FECTOR | 3:1 (Max) |
SHORT CIRCUIT PROTECTION | 5 cycles turn Off Inverter, no transfer to Bypass, provide Alarm (AC Mode), 5 cycles turn Off Inverter, provide Alarm(Battery Mode), Input Fuse blown or Breaker action |
WAVEFORM | Pure Sinewave |
TRANSFER TIME (AC Mode to Battery Mode) (Inverter to Bypass) |
ZERO <4 ms |
EFFECIENCY | 85%~ 92% |
BATTERY | |
DC VOLTAGE | 36 V |
CHARGE CURRENT | 9.5 Amps |
COMMUNICATION INTERFACE | RS232,SNMP (Optional) |
INDICATION | LCD Display |
NOISE LEVAL | Less than 50dBA @ 1 Meter (With Fan Speed Control) |
UPS OVERLOAD / UPS SHORT CIRCUIT | 110% / 300% |
WARRANTY | Two Years |